Active Thermal Hazard Monitoring and Early Warning Device
This device is specially designed for scenarios such as box-type transformers and inverters, featuring distributed installation and integrated detection to achieve early warning of overheating hazards in discrete intervals.
- Information
Application Scenarios
Suitable for box-type transformers, inverters, and other similar scenarios.
Technical Parameters
Particle diameter detection range: | 100nm-20μm |
| Particle detection resolution: | 1×10⁴ particles |
Ambient temperature monitoring: | Range: -20℃-60℃; Accuracy: ±1℃; Resolution: 0.5℃ |
| Ambient humidity monitoring: | Range: 0-95%RH; Accuracy: ±5%RH; Resolution: 1%RH |
Gas detection types: | Supports simultaneous detection of 2-4 kinds |
| Carbon monoxide detection: | Range: 0-5000ppm; Sensitivity: 2ppm |
Sampling lines & method: | Aspirating distance up to 10 meters; supports triple-channel simultaneous sampling |
| Early warning functions: | Gas alarm + 5-level particle alarm + temperature alarm |
Display screen: | 2.7-inch LCD screen |
Communication method: | Wireless/RS485/dry contact/Ethernet |
Communication protocol: | 4G, ModBus, TCP/IP |
| Input/output: | At least 2 dry contacts |
Operating power supply: | AC220V/DC24V |
Protection rating: | IP40 |
| Safety certifications: | CE certification, EMC Level IV |