Active Fire Monitoring and Early Warning Device (LX-F2WB)
The early warning device integrates dual-section nanoparticle detection, characteristic gas sensing, and active sampling technologies to achieve full-process identification and advanced alerting of overheating hazards in electrical equipment and materials.
- Information
Application Scenarios
Power distribution rooms, energy storage power stations, cable interlayers, cable tunnels, wind turbine units, data centers, etc.
Technical Parameters
Particle diameter detection range: | 2nm-20μm |
| Particle detection resolution: | 0.1×10⁴ particles |
Ambient temperature monitoring: | Range: -20℃-60℃; Accuracy: ±1℃; Resolution: 0.5℃ |
| Ambient humidity monitoring: | Range: 0-95%RH; Accuracy: ±5%RH; Resolution: 1%RH |
Carbon monoxide monitoring: | Range: 0-5000ppm; Sensitivity: 2ppm |
Sampling method: | Dual-channel independent zone detection, active sampling |
| Alarm functions: | Gas alarm + 5-level particle alarm + temperature alarm |
Communication method: | Wireless/RS485/Ethernet |
Communication protocol: | 4G, ModBus, TCP/IP |
Input/output: | ≥2 dry contacts |
Display screen size: | 7-inch LCD touch screen |
Operating power supply: | AC220V/DC24V |
Electromagnetic compatibility protection class: | EMC Level IV |
Explosion-proof rating: | ⅡCT4 |
| Protection rating: | Not less than IP40 |